Complete reference guide for the Thermotech Model 302 Series — application, installation, testing, and warranty.

Description

A. General

The 302 series automatic heat detector is designed for fire detection with alarm systems. Thermotech detectors are normally open devices and are "rate compensation type" detectors. All four models are self-restoring, hermetically sealed, shock and corrosion resistant, nonferrous, and tamper-proof.

B. Principles of Operation

The Model 302 operates on rate compensation principles. High expansion aluminum tube encases two insulated struts with opposing open contact points. Shell and struts have different expansion coefficients.

Slow Rate of Temperature Rise: Heat penetrates inner struts. Tubular shell and struts expand until rated temperature reached. Silver contact points close, initiating alarm.

Rapid Rate of Temperature Rise: Less time for heat to penetrate inner strut. Rapid shell lengthening with slower strut reaction allows contacts to close at a lower level — compensates for thermal lag in conventional fixed temperature detectors.

When ambient air drops below rated temperature, shell contracts, contacts open, detector resets automatically.

C. Specific Model Descriptions

Thermotech 302 Series includes Models 302, 302-AW, 302-ET, and 302-EPM. All available in 135°F or 194°F ratings.

General Application

A. General

Application should be based on sound engineering judgment and NFPA 72 National Fire Alarm Code and/or local authority having jurisdiction.

B. Cross-Zoning Requirement

When used with automatic fire suppression systems (pre-action, deluge sprinklers, CO2, halon, dry chemical), Thermotech requires at least two detectors to initiate alarm response. This cross-zoning eliminates premature discharge. Refer to NFPA 72.

C. Maximum Ceiling Temperatures

Detector Rated TempMin Ambient AirMax Ceiling Temp
135°F-40°F100°F
194°F-40°F150°F

Example: Residential garage with max ceiling temp 103°F two days/year — use 194°F detector. Ceiling never above 100°F — use 135°F detector.

D. Temperature Fluctuation Considerations

  • •135°F detectors: Should not respond to fluctuations less than 30°F/min between 60°F–100°F.
  • •194°F detectors: Should not respond to fluctuations less than 50°F/min between 60°F–150°F.

Do not install in hot air ducts, in front of heaters, or paint booths using heat to cure.

E. Direct Heat Sources

Aluminum tube collects heat from radiating sources. Keep out of direct sunlight and away from heaters and heat ducts.

Application of Specific Models

A. General

Based on NFPA 72 and local authority. Detectors not directionally affected — mount horizontally or vertically.

B. Listed Spacing

Based on smooth ceilings up to 10' high. Refer to NFPA 72 for non-smooth or higher ceilings. RTI Classification: 135°F = Quick, 194°F = V Fast.

Listing302302-AW302-ET302-EPM
UL50'×50'50'×50'50'×50'40'×40'
FM 135°F20'×20'20'×20'20'×20'Not Listed
FM 194°F30'×30'30'×30'30'×30'Not Listed
Horizontal UL40'×40'40'×40'40'×40'30'×30'

C. Model 302

Basic model. Interior vertical mounting, compatible with terminal screw connections.

D. Model 302-AW

All-weather with four wire leads. Hermetically sealed, moisture/dust proof. Vertical mounting.

E. Model 302-ET

Same as 302-AW with high-temp polycarbonate hexagonal grip bushing, 1/2" conduit threads. Vertical or horizontal. Hand tighten only.

F. Model 302-EPM

Explosion proof for hazardous locations. Division 1, Class I Groups C&D, Class II Groups E, F, G. Interior use only. Hand tighten only.

G. AP-P Adaptor Plate

Decorative white polycarbonate adapter plate for 302 and 302-AW on 3" outlet or 4" octagon boxes.

Maintenance

Model 302 series is low maintenance. Auto-restore when temps drop below rating. Dust/dirt accumulation should not affect detectors. For aesthetic cleaning: turn alarm off, clean with damp cloth. Precision devices — DO NOT DROP or expose to excessive vibration.

Testing

A. General

Refer to NFPA 72 for testing frequency, record keeping, and considerations.

B. Testing Methods

1. Operation Test

Heat detector with common hair dryer. No open flames. Should operate shortly after hot air applied. Can test before or after installation.

2. Sensitivity Test

Requires convection laboratory oven with controlled temperature and calibrated measuring devices. Maintain 20°F below rating for 5 minutes, increase at 1°F/min. Connect to 6V power source and signaling means. Air constantly circulating.

Warranty

Thermotech warranties Model 302 series for one year against defects in material or workmanship. Limited to proper maintenance, testing and installation per NFPA and local authority. Purchaser responsible for testing suitability. Thermotech liability limited to detector purchase price. Installation costs are purchaser's responsibility.

Reference Tables

Special Considerations

Temp RatingMax CeilingMin Ambient
135°F100°F-40°F
194°F150°F-40°F

Electrical Rating

VoltageCurrent
6–125 VAC5 amps
6–25 VDC1 amp
125 VDC0.5 amp

Need Technical Documentation?